Small motor branch circuits and control transformer primaries need a fuse that rides out inrush without giving up short-circuit protection. The Littelfuse FLSR010 is a 10 A, 600 VAC Class RK5 dual-element time-delay fuse from the POWR-GARD FLSR series, with a 200,000 A AC interrupting rating. This listing is a package of 10, sized for maintenance crib and service van stock.
Why maintenance electricians pick it
- Dual-element time delay tolerates motor starting and transformer inrush current.
- Class RK5 fits Class R rejection-style fuse clips in disconnects and combination starters.
- Rated 600 VAC and 300 VDC, with 200 kA AC and 20 kA DC interrupting ratings.
- Standard 13/16 in by 5 in ferrule body for 600 V, 0 to 30 A fuse holders.
- Package of 10 keeps spares on hand for three-phase disconnects.
Specifications
| Spec |
Detail |
| Brand |
Littelfuse (POWR-GARD) |
| Model |
FLSR010 (FLSR series) |
| Class |
UL Class RK5, dual-element time delay |
| Ampere rating |
10 A |
| Voltage rating |
600 VAC / 300 VDC |
| Interrupting rating |
200 kA AC / 20 kA DC |
| Size |
13/16 in dia. x 5 in long, ferrule |
| Package |
10 fuses |
Pro tip from the counter
On a control power transformer primary, a time-delay fuse like this can ride through the magnetizing inrush that pops fast-acting fuses at the same rating. Pick the size from the transformer maker's primary fuse chart for its VA and primary voltage rather than defaulting to 10 A.
Best for: motor branch circuits, control transformer primaries, fused disconnect switches, plant maintenance stock
We ship across Canada from Vaughan, ON. Stocking a plant crib? Get trade pricing with a quote or at (905) 553-7171.