Standard 14/2 NMD90 non-metallic sheathed building cable with a bare bonding conductor, supplied in a 75 metre coil. This is the everyday residential branch circuit cable for receptacles, switches and lighting in dry and damp locations. Pricing follows the copper market, so the listing is by enquiry rather than a posted figure.
Why a copper cable is quoted rather than priced
The copper in a coil of building wire is a traded commodity, and the price a distributor pays changes week to week. Posting a fixed figure on a cable listing means either quoting high enough to be safe or re-pricing the page constantly, and neither helps a contractor pricing a job. A phone quote gets you the number that is actually good today, and for a house lot it is usually a better number than a posted one would have been.
Specifications
| Cable type |
NMD90 non-metallic sheathed cable |
| Conductors |
COPPER CONDUCTORS |
| Construction |
14 AWG, 2 conductors, 1 strand, bare 14 AWG ground conductor |
| Voltage and temperature rating |
300 VOLTS / -25ºC MIN, 90ºC MAX |
| Insulation and jacket |
PVC / NYLON INSULATION, PVC JACKET |
| Standards |
ASTM; CSA C22.2 No. 48 (non-metallic sheathed cable); Canadian Electrical Code |
| Allowable ampacity |
25 A* (* In accordance with the 2015 Canadian Electrical Code Part I Rule 14-104(2)) |
| Applications |
may be used for both exposed work in dry locations or concealed work in dry or damp locations |
| Minimum installation temperature |
-25°C for two-conductor cables |
| Approximate dimensions |
0.388 x 0.192 inches (9.86 x 4.88 mm) |
| Approximate weight |
68 lb/1000ft (101 kg/km) |
| Coil length |
NMD 14/2 75M |
Pro tip from the counter
The ampacity column and the breaker size are two different numbers, and the datasheet itself puts an asterisk on that figure pointing at Rule 14-104(2). Read the rule alongside the table before you size the overcurrent device, because an inspector will quote the rule and not the table.
Best for: residential rough-in, renovation and service work where dry or damp location branch circuit cable is going in by the coil rather than by the metre.
Common questions
What does the 90 in NMD90 mean?
It is the maximum allowable conductor temperature in degrees Celsius. The insulation is built to withstand that, which is a different question from how much current the Code will let you run through the cable.
Can I run this cable outdoors or in a wet location?
No. The datasheet limits it to exposed work in dry locations or concealed work in dry or damp locations. Wet locations, direct burial and outdoor runs all need a different cable.
Is the 25 amp ampacity figure my breaker size?
No, and this is the mistake that gets caught on inspection. The ampacity table and the overcurrent rule are two different things, and the datasheet flags Rule 14-104(2) against that figure for exactly this reason.
How cold can it be when I pull it?
The datasheet gives a minimum recommended installation temperature for two conductor cable and asks that the coil be stored above freezing for a full day beforehand. Cold jacket cracks, and it cracks where you cannot see it.