Small pumps, fans and conveyors often need overload protection and an emergency stop right at the machine. The Lovato SM1P0160EKIT pairs an SM1P0160 push-button manual motor starter (motor protection circuit breaker), adjustable from 1 to 1.6 A, with an SM1Z1712P surface-mount enclosure rated IP65 / UL Type 4X that carries an emergency stop button. It is a ready-to-mount enclosed starter for wet, wash-down and outdoor locations.
Why maintenance electricians pick it
- Thermal overload adjustable 1 to 1.6 A with magnetic short-circuit protection.
- Trip class 10A with phase failure detection.
- Emergency stop button built into the enclosure.
- IP65 / UL Type 4X enclosure rated -25°C to +60°C.
- cULus; breaker complies with UL 508 and CSA C22.2 No. 14.
Specifications
| Spec |
Detail |
| Brand |
Lovato Electric |
| Model |
SM1P0160EKIT (SM1P0160 + SM1Z1712P) |
| Device |
3-pole manual motor starter / MPCB, push button |
| Thermal adjustment |
1 to 1.6 A |
| Trip class |
10A, phase failure sensitive |
| UL/CSA HP rating (3-phase) |
3/4 HP at 440-480 V; 1 HP at 550-600 V |
| Breaking capacity (IEC Icu) |
100 kA at 230-690 V |
| Enclosure |
SM1Z1712P surface mount, IP65 / UL Type 4X, with emergency stop button |
| Enclosure width |
100 mm |
| Operating temperature |
-25°C to +60°C |
| Approvals |
cULus; UL 508, CSA C22.2 No. 14 |
Pro tip from the counter
The e-stop and the breaker handle only open the load side; the line terminals inside the enclosure stay live from the feeder. Before anyone opens the cover or works on the motor, lock out the upstream disconnect or breaker. Pressing the e-stop is not a lockout.
Best for: 600 V pumps and fans, conveyors and small process motors, wash-down and outdoor machine locations, OEM and maintenance replacements
Ships across Canada from Vaughan, ON. For multiple starters or other ranges, get trade pricing with a quote or at (905) 553-7171.