Starting and switching large motors, heaters and feeders takes a contactor built for heavy current and frequent operation. The Techspan LC1FDP500A is an F-Line 3-pole IEC contactor rated 500 A AC-3 (280 kW class) and 700 A AC-1, sold without a coil so you can order the control voltage the panel uses. Techspan rates it up to 400 HP at 480 V and 500 HP at 600 V three-phase.
Why panel builders pick it
- 500 A AC-3 for motor starting and 700 A AC-1 for resistive loads.
- Coil ordered separately (F500 frame: LX1FK AC or LX4FK DC series) to match any control voltage.
- Bolt terminals take bus bar or large cable lugs.
- Mechanical interlock LA9FK976 available for reversing pairs.
- Rated for 10 million mechanical operations; UL and CSA approved for standard fault ratings, per Techspan data.
Specifications
| Spec |
Detail |
| Brand |
Techspan (F-Line) |
| Model |
LC1FDP500A |
| Poles |
3 (NO) |
| AC-3 rating |
500 A (280 kW class) |
| AC-1 rating |
700 A |
| Max HP, 3-phase |
150 HP at 200 V; 200 HP at 230 V; 400 HP at 480 V; 500 HP at 600 V |
| Coil |
Not included; F500 coils LX1FK..V (AC) / LX4FK..V (DC) |
| Rated operating voltage |
Up to 1,000 V |
| Connections |
2 x 240 mm² cable lugs or 40 x 5 mm bars, M10 bolts, 35 Nm |
| Mechanical life |
10 million operations |
| Approvals |
UL, CSA (standard fault ratings), IEC 60947-4-1 |
Pro tip from the counter
Don't size it from the 280 kW figure in the title, which is an IEC rating at around 400 V. On Canadian 600 V or 480 V motors, check the motor's HP and FLA against Techspan's HP table for your voltage, and order the matching LX1FK coil for the control voltage at the same time, since the contactor ships without one.
Best for: large motor starters, pump and fan drives, industrial feeders and heater banks, reversing starters with interlock, OEM and panel shop builds
Downloads: F-Line contactor spec sheet (PDF)