Very small three-phase motors on fans, pumps and conveyors still need overload protection and a local on/off. The Lovato SM1P0025KIT is a manual motor starter kit that pairs an SM1P0025 push-button motor protection circuit breaker, adjustable from 0.16 to 0.25 A, with an SM1Z1711P surface-mount enclosure rated IP65 and Type 4X. It gives maintenance crews an enclosed manual motor starter in one part number.
Why maintenance electricians pick it
- Adjustable 0.16 to 0.25 A thermal setting for small fractional motors.
- Phase-loss detection helps protect three-phase motors from single phasing.
- IP65 / Type 4X surface enclosure suits wet or washdown areas.
- Push-button start and stop right at the machine.
- cULus listed components; IEC Icu 100 kA at 400 V.
Specifications
| Spec |
Detail |
| Brand |
Lovato Electric |
| Kit |
SM1P0025KIT |
| Components |
SM1P0025 manual motor starter + SM1Z1711P enclosure |
| Poles |
3 |
| Setting range |
0.16 to 0.25 A |
| Control |
Push button |
| Trip class |
10A (IEC) |
| Phase-loss detection |
Yes |
| Enclosure |
Surface mount, IP65 / Type 4X, 100 mm wide |
| Enclosure operating temperature |
-25 to +60°C |
| Certifications |
cULus; UL 508, CSA C22.2 No. 14; not UL Type E |
Pro tip from the counter
Lovato lists the SM1P as not UL Type E, so in North America treat it as a manual motor controller with overload protection, not as the branch-circuit protection. Have the electrician put fuses or a breaker upstream, sized per the CEC, and set the dial to the motor nameplate FLA.
Best for: small conveyor and fan motors, dosing and sump pumps, washdown areas, OEM machine retrofits
Ships across Canada from Vaughan, ON. For plant quantities, request pricing through a quote or (905) 553-7171.